Context Plus XFP502E/X/CON XFP Networkable Two Loop 32 Zone Addressable Panel

♦ Context Plus XFP502E/X/CON
♦ Third-party certificated to EN54 parts 2 and 4 by the LPCB.
♦ Full compatibility
♦ InterConnect Up To Eight XFP Main Panels
♦ Four XFP Repeater Panels Per Main Two Wire RS485 Network.
♦ Two Independently Programmable Conventional Sounder Circuits.
♦ Two Programmable Inputs.
♦ A Fault Output Relay & Three Programmable Relay Outputs With Voltage
♦ Three Zone Dependency Functions (A, B & C to EN54-2 Clause 7.12)
♦ A Day/Night Function.
♦ An Investigation Delay Period Function.
♦ Individual Sensitivity Settings For Each Device
♦ Powerful Short Circuit Protected Loop Drivers
♦ An Integral EN54 Switch Mode PSU rated @ 185-260V a.c. 50/60Hz (3A on 32 zone panel, 1.4A on 16 zone panel)
♦ Earth Fault Monitoring
♦ 12 Months Warranty

Call Us:

0185-3330344, 01711-461346

Office Locations: Uttara | Malibagh

Description

Context Plus XFP502E/X/CON Bangladesh, Context Plus 2 Loop Zone Panel Bangladesh

BRANDContext Plus
ModelXFP502E/X/CON
Main supply230V a.± 10% 50/60Hz. Max current 680mA
Internal power supply27V d.c Nominal
Total output current limited to3A @ 230 V a.c.
Supply and battery charger monitored for failureYes
Batteries monitored for disconnection and failureyes
Batteries protected against deep dischargeyes
Max. battery size and type7.0 Ahr VRLA
Specified batteries for LPCB approved systems2 x Yuasa NP7-12
Quiescent current drain (1 loop unloaded)< 80mA
Quiescent current drain (2 loop unloaded)<100mA
Earth fault monitoringYes (any conductor)
Temperature compensated chargingYes
Number of loop drivers(XFP501/CON) 2 (XFP502/CON
Line monitored for open and short circuit faultsYes
Onboard loop isolators with LED indication when activeYes
Auto-polling from each loop enYes
Max. loop output current500mA (Voltage: 25V min, 34V max)
Max. number of addressable devices per loop126
Number of programmable sounder groups16
Number of programmable output sets16
Number of programmable circuits2
End of line resistor valueYes
End of line resistor value6800 Ω 5% Tol. 0.25 W
Line monitored for open and short circuit faultsYes
Outputs fused at400mA
Max. number of sounders @ 20mA80
TypeRelay voltage free single pole changeover
Max switching current1A
Max switching voltage30 V d.c
FaultActive when no faults are present
‘24V’ Aux Power Output19.5V min, 28V max. Max current 100mA. Protected by resettable overload circuit
Input 1Connectto 0V to trigger. Max input voltage 27V d.c. (non-latching). Programmable from cause and effect.
Input 2Connectto 0V to trigger. Max input voltage 27V d.c (non-latching). Programmable from cause and effect.
Mains Fuse1A HRC Ceramic 20mm
Battery Fuse – limits the current drawn from the battery3.15A F 20mm
Control buttonsSilence, Reset, Resound, Investigate; More Information; Menu
Event scrolling and menu access buttonsUp (1); Down (2); Accept (3); Abort (4)
Liquid Crystal DisplayTwo lines x 40 characters, backlit
Number of Zonal LED indicators32
Approx. dimensions of back box (W x H x D410 x 250 x 80mm (metal)
Approx. dimensions of lid (W x H x D)439 x 274 x 7mm (metal)
Approx. weight (without batteries)4.5kg
Type of cableFire resistant screened cable, minimum size 1mm2
Max. cable length per loop1km
Connector blocksPlug-on type, largest acceptable conductor size 1.5mm2
Max. allowable loop impedance (each conductor20Ω
Max. cable capacitance.27µF
ConnectionVia AFP711 network driver card fitted at main panel
Temperature range-5 to +40oC
Maximum relative humidity95%
Warranty12 Months